Plug-In, Repeat Cycle Timers, TNK Timers, Airotronics,

  Products

Plug-In Repeat Cycle Timers - TNK Timers


Plug-In Repeat Cycle Timers - TNK Timers
TNK Timers

The TNK Repeat Cycle units meet the needs of customers who require IC digital timing circuits with octal, magnal round and QC bases for plug-in installation. The units are available in SPDT, DPST and DPDT relay forms up to 10 amp with fixed or adjustable time periods.

  Download

Timing Mode

Application of input voltage to the timer starts the “Off” time delay. At the end of the “Off” time delay, the “On” time delay starts, and the relay is energized. At the end of “On” time delay the relay is de-energized, the timer returns to the “Off” time delay, and cycling continues as long as input voltage is applied. Removal of the input voltage resets the timer. The “Off” and “On” times are equal.

FEATURES
  • CMOS IC digital timing
  • Multi-board construction
  • Relays are sealed
  • Proven circuitry
  • Standard octal (8 pin), magnal (11 pin) plug-ins or 4.75 mm (.187") blade terminal mountings
  • Fixed or variable time adjustment
  • Optional remote time adjustment
  • Timing ranges from .05 to 1000 seconds standard (special time settings and ranges up to 72 hours also available)
  • 0.1% Repeat accuracy
  • 100% Operational testing before shipping

BASIC WIRING AND DIMENSIONS
SPECIFICATIONS

Input Voltages:

  • VAC: 12, 24, 120, 230, 50/60 Hz
  • VDC: 12, 24

Operating Voltage: 20% of nameplate voltage

Relay Contact Ratings: 5 amps DPDT, 10 amps DPDT Optional

Repeat Accuracy: 0.1% under fixed operating conditions

Reset Time: 50 milliseconds

Tolerances:

    Fixed: 10%, Optional: 5%, 1% Variable: +20%, -0, Optional: +10%, -0%
Note:Tolerances on variable units are with respect to upper limit only. Timers with time periods greater than 10 sec. will have a 100 to 1 ratio, i.e., 1 to 100 seconds, 30 to 3000 seconds. Timers with the time periods less than 10 sec., will have a 10 to 1 ratio, i.e., .99 to 9.9 seconds, .5 to 5 seconds.

Life Expectancy:

  • Mechanical: 1 million operations
  • Electrical: Up to 100,000 operations at full current load

Protection:

  • Polarity Protection: All DC units have reverse polarity protection.
  • Transient Protection: 25 joules

Temperature Ranges:

  • Storage: -40° C to +85° C
  • Operating: -25° C to +85° C

Housing Material: High impact, UL approved black Lexan

SELECTION PROCEDURE
Mode of Operation Series Input Voltage Time Ranges Tolerance Time Adjustment Method Base Style Options
Repeat-Cycle Off/On Delay TNK
  1. 120 VAC
  2. 230 VAC
  3. 24 VAC
  4. 24 VDC
  5. -
  6. -
  7. 12 VDC
  8. special ac
  9. special Dc

VARIABLE TIME PERIODS
0001 .1 to 1 sec.
0010 .1 to 10 sec.
0100 1 to 100 sec.
1000 10 to 1000 sec.

Any range up to 72 hours available on special order.

FIXED TIME PERIODS
Specify time in full seconds or hours followed by the letter “S” or “H” and the decimal amount of the main time unit.
Examples:
  • 5S5 is 5.5 seconds
  • 5H5 is 5.5 hours

X

    Standard (Fixed: 10% Variable: +20% -0%)

E

    Optional (Fixed, 5%)

F

    Optional (Fixed, 1%)

G

    Optional (Adjust.: +10%, -0%)

A

    Variable knob on timer

B

    Variable with external potentiometer AOT supplied

C

    Factory-fixed time

D

    Fixed time with customer supplied resistor

1

    8 Pin Round Octal Base

2

    11 Pin Round Magnal Base

3

    11 Pin Spade .187 Quick Connect

X

    Standard 5 amps

H

    10 amps (8 amps ul Recognized for USA and Canada.)