CS Current Sensor
CS Current Sensor
 |
CS Current Sensor
The CS is an over or undercurrent sensing control. The toroidal sensor means no break in the power wiring and the combination of the overcurrent LED, current, and percentage trip adjustment provides easy and accurate setting. It can handle loads up to 20 amps with time delays up to 100 secs.
Timing Mode
When the sensed current increases above or falls below the set-point, the time delay will start. At the end of the delay, the output will be energized.
Download
|
 |
|
FEATURES |
- Overcurrent and undercurrent sensing
- Toroidal sensing provides complete isolation between sensed current and control circuit
- Easy setting of trip point with unique combination of LED indicator, current adjustment and percentage potentiometers.
- Can switch up to 20 amps (1.5 HP)
- Totally encapsulated for protection from harsh environments
|
-
Single screw mounting
-
Transient and polarity protected
-
No heat sinking required
-
CMOS time delay
- 100% Operational testing before shipping

|
| BASIC WIRING AND DIMENSIONS
|
|
| SPECIFICATIONS
|
Input Voltage: +20%/-10% - VDC: 12 or 24
- VAC: 24, 120, 230, 50/60 Hz
Time Delay:
- Timing Mode: Delay After Sense
- Type: Digital CMOS
- Time Range: 0.1 seconds to 10 seconds
(adjustable) 1 to 100 seconds (fixed) - Repeatability: 0.5%
- Setting Accuracy: 5% or 50 ms.,
whichever is greater - Reset Time: 100 milliseconds
Relay Life Expectancy:
- Mechanical: Up to 10 million operations
- Electrical: 100,000 operations at max. load
|
Protection:
- Polarity Protection: All DC units have reverse polarity protection
- Transient Protection: 18 joules
- Dielectric Strength: 1800V RMS 60 Hz
Temperature Ranges:
- Storage: -40°C to +85°C
- Operating: -25°C to +85°C
Sensor:
- Toroid - Through hole wiring
- Current Range: 1 to 20 amps
- Frequency: 50/60 Hz
- Trip Point Hysteresis: 5% typical
- Trip Point Drift vs Temperature: 2% typical,
5% max - Fixed Setting Accuracy: 5%
|
| SELECTION PROCEDURE
|
| Mode of Operation |
Series |
Relay Common |
Input Voltage |
Current Sensing |
Fault Indic. |
Hyster-esis |
Time Delay |
Time Adj. Method |
Current Set Point |
Current Adj. Method |
Percent Adj. |
Outputs |
| Current Sensor |
CS |
B = Hot * = Isolated |
- 120 VAC
- 230 VAC
- 24 VAC
- 24 VDC
- 12 VDC
|
O = Over U = Under |
F = Yes * = No |
* = 0 H =5% |
VARIABLE TIME PERIOD
010 .1 to 10 secs
FIXED TIME PERIOD
Specify time in full seconds from 1 to 100 |
C = Fixed
A = Integral knob |
VARIABLE SET POINT
020 .1 to 20 amps
FIXED SET POINT
Specify amps from 1 to 20 amps |
C = Fixed
A = Integral knob |
* = 0
P = 20% |
H Heavy duty 10 amps (6 amps relay standard)
J 20 amps (1.5 HP) |
|
|